VEGATOR 122 - Controller for level detection with relay output

VEGATOR 122 - Controller for level detection with relay output

Share:


VEGATOR 122 - Controller for level detection with relay output



Double channel controller for level detection

Transmission of 8/16 mA signals for level signalling (double channel)

Application area

The VEGATOR 122 is a signal conditioning instrument for level detection for the vibrating level switches VEGASWING, VEGAVIB and VEGAWAVE with electronics version ''Two-wire“. With this instrument simple control tasks can be solved. Typical applications are monitoring functions such as overflow or dry run protection.

Advantages

  • Comprehensive monitoring detects short-circuit and line break of the measuring cable and interferences in the sensor
  • Simple and comfortable SIL and WHG function test by means of test key
  • Simple installation through carrier rail mounting as well as detachable, coded terminals

Technical data

Input 2 x sensor input two-wire 8/16 mA
Output 2 x relay output (SPDT)
Operating voltage 20 … 253 V AC, 50/60 Hz
Mounting carrier rail 35 x 7.5 acc. to EN 50022
SIL qualification optionally up to SIL2

Refer to the link for more details: https://www.vega.com/en/home_de/products/product-catalog/signal-conditioning/controllers/vegator-122